13. Before making a service call
- Trip information and remedies
13.1 Trip /Alarm causes and remedies
When a problem arises, diagnose it in accordance with the following table.
If it is found that replacement of parts is required or the problem cannot be solved by any remedy described in the
table, contact your Toshiba distributor.
[Trip information]
Error code
Failure code

0001

0002

0003

0004

0005
0008
*

0009
*


000A
* This marking trips can be selected valid or invalid by parameters.
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.ctiautomation.net - Email: info@ctiautomation.net
Problem
 The acceleration time  is too short.
Overcurrent during
acceleration
 The V/F setting is improper.
 A restart signal is input to the rotating
motor after a momentary stop, etc.
 A special motor (e.g. motor with a small
impedance) is used.
 Low inductance motor especially High
speed motor is used.
 The deceleration time  is too short.
Overcurrent during
deceleration
 Low inductance motor especially High
speed motor is used.
 The load fluctuates abruptly.
Overcurrent during
 The load is in an abnormal condition.
constant speed
operation
 Low inductance motor especially High
speed motor is used.
 The insulation of the output main circuit or
Overcurrent (An
overcurrent on the
motor is defective.
 The motor has too small impedance.
load side at start-up)
 A main circuit element is defective.
Overcurrent at start-
up
 A phase failure occured in the input line of
Input phase failure
the main circuit.
 The capacitor in the main circuit lacks
capacitance.
 A phase failure occurred in the output line
Output phase failure
of the main circuit.
 The input voltage fluctuates abnormally.
Overvoltage during
acceleration
(1) The power supply has a capacity of
500kVA or more.
(2) A power factor improvement capacitor is
opened or closed.
(3) A system using a thyristor is connected
to the same power distribution line.
 A restart signal is input to the rotating
motor after a momentary stop, etc.
Possible causes
 Increase the acceleration time .
 Check the V/F parameter setting.
 Use  (auto-restart) and 
 In case of pt=0, 1, 7, decrease vb.
 In case of pt=2 to 6, set f415
 Choose the higher power range drive.
 Increase the deceleration time .
 Choose the higher power range drive.
 Reduce the load fluctuation.
 Check the load (operated machine).
 Choose the higher power range drive.
 Check the secondary wiring and insulation
 Set f613=2, 3
 Contact your Toshiba distributor.
 Check the main circuit input line for phase
 Check the capacitor in the main circuit for
 Check the main circuit output line, motor,
 Select output phase failure detection
 Insert a suitable input reactor.
 Use  (auto-restart) and 
M-1
E6581611
Remedies
(ride-through control).
(Motor rated current) and make an auto-
tuning.
(1 class up drive is recommended.)
(1 class up drive is recommended.)
(1 class up drive is recommended.)
state.
failure.
exhaustion.
etc. for phase failure.
parameter f605.
(ride-through control).
(Continued overleaf)