The space shown in the diagram is the minimum allowable space. Because air cooled equipment has cooling
fans built in on the top or bottom surfaces, make the space on top and bottom as large as possible to allow
for air passage.
Note:
1
 Calorific values of the inverter and the required ventilation
About 5% of the rated power of the inverter will be lost as a result of conversion from AC to DC or from DC to
AC. In order to suppress the rise in temperature inside the cabinet when this loss becomes heat loss, the
interior of the cabinet must be ventilated and cooled.
The amount of forcible air-cooling ventilation required and the necessary heat discharge surface quantity
when operating in a sealed cabinet according to motor capacity are as follows.
Voltage class
Three-phase
200V class
Single-phase
200V class
Three-phase
400V class
Note 1) Case of 100% Load Continuation operation. The heat loss for the optional external devices (input AC
Note 2) It is power consumption when power is on but is not output (0Hz), and cooling fan is activated (model
Do not install in any location where there is high humidity or high temperatures and where there are
large amounts of dust, metallic fragments and oil mist.
Calorific values (W)
Inverter type
4kHz
22
2002PM
35
2004PM
45.6
2007PM
81
2015PM
94.9
2022PM
VFS15-
139
2037PM
2055PM
256
2075PM
305
2110PM
475
2150PM
557
2002PL
23
2004PL
37
VFS15S-
2007PL
46
2015PL
79
2022PL
101
30
4004PL
39
4007PL
58
4015PL
77
4022PL
131
VFS15-
4037PL
4055PL
211
4075PL
254
4110PL
387
4150PL
466
reactor, radio noise reduction filters, etc.) is not included in the calorific values in the table
with cooling fan).
Amount of forcible air
cooling ventilation
Note 1)
3
required (m
/min)
12kHz
4kHz
12kHz
24
0.12
0.14
0.20
0.23
40
50
0.26
0.28
0.46
0.52
92
104
0.54
0.59
154
0.79
0.87
1.45
1.61
283
367
1.73
2.08
2.70
3.05
538
628
3.16
3.56
24.8
0.13
0.14
42.2
0.21
0.24
50
0.26
0.28
90
0.45
0.51
110
0.58
0.62
0.17
0.22
39
50
0.22
0.28
0.33
0.43
76
102
0.44
0.58
156
0.75
0.88
1.20
1.49
263
346
1.44
1.96
2.20
2.67
470
572
2.65
3.25
A-32
E6581926
Heat discharge surface
Standby
area required for
power
sealed storage cabinet
requirement
3
(m
)
(W)
Note 2)
4kHz
12kHz
0.44
0.48
6
0.70
0.80
6
0.91
0.99
6
1.61
1.85
10
1.90
2.07
10
2.77
3.08
11
5.12
5.66
22
6.10
7.34
22
9.50
10.76
31
11.14
12.56
31
0.50
0.46
5
0.74
0.84
5
0.92
1.00
5
1.57
1.80
8
2.03
2.20
8
0.61
0.78
12
0.78
1.00
12
1.15
1.53
12
1.53
2.04
13
2.63
3.12
13
4.22
5.26
22
5.08
6.92
22
7.74
9.40
31
9.32
11.44
31