Toshiba Tosvert VF-S15 Instruction Manual page 140

Industrial inverter (for 3-phase induction motors)
Hide thumbs Also See for Tosvert VF-S15:
Table of Contents

Advertisement

(2) [f105 = 1 (Stop)]: If an F command and an R command are entered simultaneously,
Output frequency [Hz]
Setting frequency
Forward run command
Reverse run command
6.6.2
Changing the voltage range of VIB terminal
f107 : Analog input terminal selection (VIB)
 Function
This parameter allows you to choose the voltage signal input for the VIB terminal.
[Parameter setting]
Title
Function
Analog input terminal
f107
selection (VIB)
● f107=0 : Input 0 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/1000 between 0 to +10Vdc.
● f107=1 : Input -10 to +10Vdc to VIB-CC terminals.
Resolution is maximum 1/2000 between -10 to +10Vdc.
the motor will deceleration stop.
0
Adjustment range
0: 0-+10V
1: -10-+10V
F-29
E6581926
Forward run
Time[s]
Reverse run
ON
OFF
ON
OFF
6
Default setting
0