Technical Specification; Power Ratings - Omron 3G3MX2 Quick Start Manual

Born to drive machines; 200 v class three-phase input 0.1 to 15 kw; 200 v class single-phase input 0.1 to 2.2 kw; 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

MX2 Quick Start Guide

1.2 Technical specification

Model number
3G3MX2
Control methods
Output frequency range
Frequency precision
Resolution of frequency set value
Resolution of output frequency
Starting torque
Overload capability
Frequency set value
V/f Characteristics
Analogue inputs
Pulse train input terminal
Accel/Decel times
Display
Motor overload protection
Instantaneous overcurrent
Overload
Overvoltage
Undervoltage
Momentary power loss
Cooling fin overheat
Stall prevention level
Ground fault
Degree of protection
Ambient humidity
Storage temperature
Ambient temperature
Installation
Installation height
Vibration

1.3 Power ratings

Item
3G3MX2 inverters, 200 V models
kW
Applicable
motor size
HP
200 V
Rated capacity
(kVA)
240 V
Rated input voltage
Rated output voltage
Rated output current (A)
Starting torque
Without resistor
Braking
With resistor
DC braking
Weight
4
Phase-to-phase sinusoidal pulse with modulation PWM (Sensorless vector control, V/F)
0.10..1000.00 Hz (with restrictions above 400Hz)
Digital set value: ±0.01% of the max. frequency
Analogue set value: ±0.2% of the max. frequency (25 ±10 ºC)
Digital set value: 0.01 Hz
Analogue set value: 1/1000 of maximum frequency
0.01Hz
200% / 0.5Hz
Dual rating: Heavy duty (CT): 150% for 1 minute / Normal Duty (VT): 120% for 1 minute
0 to 10 VDC (10KW), 4 to 20mA (100W), RS485 Modbus, Network options
Constant/ reduced torque, free V/f
2 analogue inputs 0 to 10V (10KW), 4 to 20mA (100W)
0 to 10V (up to 24V), up to 32KHz
0.01 to 3600.0s (line/curve selection), 2nd accel/decel setting available
Status indicator LED's Run, Program, Alarm, Power, Hz, Amps
Electronic Thermal overload relay and PTC thermistor input
200% of rated current
Dual rating: Heavy duty (CT): 150% for 1 minute / Normal Duty (VT): 120% for 1 minute
800V for 400V type and 400V for 200V type
345V for 400V type and 172.5V for 200V type
Following items are selectable: Alarm, decelerates to stop, decelerates to stop with DC bus controlled, restart
Temperature monitor and error detection
Stall prevention during acceleration/deceleration and constant speed
Detection at power-on
IP20, Varnish coating on PCB & IP54 (For 3G3MX2-D@ type)
90% RH or less (without condensation)
-20 ºC..+65 ºC (short-term temperature during transportation)
-10°C to 50°C (Output current derating could be necessary above 40ºC or depending on installation conditions)
Indoor (no corrosive gas, dust, etc.)
Max. 1000 m
2
5.9 m/s
(0.6G), 10 to 55 Hz
AB001
VT
0.2
CT
0.1
VT
1/4
CT
1/8
VT
0.4
CT
0.2
VT
0.4
CT
0.3
VT
1.2
CT
1.0
kg
1.0
lb
2.2
Specifications
Single-phase 200 V class Specifications
AB002
AB004
0.4
0.55
0.2
0.4
1/2
3/4
1/4
1/2
0.6
1.2
0.5
1.0
0.7
1.4
0.6
1.2
Single-phase: 200 V-15% to 240 V+10%, 50/60 Hz±5%
3-phase: 200 to 240 V (proportional to input voltage)
1.9
3.5
1.6
3.0
200% at 0.5 Hz
100%: at50 Hz
50%: at 60 Hz
150%
Variable operating frequency, time, and braking force
1.0
1.1
2.2
2.4
AB007
AB015
1.1
2.2
0.75
1.5
1.5
3
1
2
2.0
3.3
1.7
2.7
2.4
3.9
2.0
3.3
6.0
9.6
5.0
8.0
70%: at 50 Hz
50%: at 60 Hz
1.4
1.8
3.1
4.0
MX2 Quick Start Guide
AB022
3.0
2.2
4
3
4.1
3.8
4.9
4.5
12.0
11.0
20%: at 50 Hz
20%: at 60 Hz
100%
1.8
4.0