MX2 Quick Start Guide

1 SPECIFICATIONS

1.1 Upon receipt

Please perform the following task after receiving the drive:
Inspect the driver for damage. If the drive appears to be damaged upon receipt, contact your supplier
Verify the receipt of the correct model by checking the information on the nameplate. If you have received the wrong model
contact your supplier.
Refer to the User's Manual for detailed information about the product and functions
Basic specifications and EMC filter
Type
Voltage
IP20
3G3MX2-AB001-E
3G3MX2-DB001-E/EC
3G3MX2-AB002-E
3G3MX2-DB002-E/EC
3G3MX2-AB004-E
3G3MX2-DB004-E/EC
1 x 230 V
3G3MX2-AB007-E
3G3MX2-AB015-E
3G3MX2-AB022-E
3G3MX2-A2001-E
3G3MX2-D2001-E/EC
3G3MX2-A2002-E
3G3MX2-D2002-E/EC
3G3MX2-A2004-E
3G3MX2-D2004-E/EC
3G3MX2-A2007-E
3G3MX2-D2007-E/EC
3G3MX2-A2015-E
3 x 230 V
3G3MX2-A2022-E
3G3MX2-A2037-E
3G3MX2-A2055-E
3G3MX2-A2075-E
3G3MX2-A2110-E
3G3MX2-A2150-E
3G3MX2-A4004-E
3G3MX2-A4007-E
3G3MX2-A4015-E
3G3MX2-A4022-E
3G3MX2-A4030-E
3 x 400 V
3G3MX2-A4040-E
3G3MX2-A4055-E
3G3MX2-A4075-E
3G3MX2-A4110-E
3G3MX2-A4150-E
* 3G3MX2-D types include a built in EMC filter
MX2 Quick Start Guide
HD (150% overload for 60s)
IP54
Max Motor (KW)
0.1
0.2
0.4
3G3MX2-DB007-EC
0.75
3G3MX2-DB015-EC
1.5
3G3MX2-DB022-EC
2.2
0.1
0.2
0.4
0.75
3G3MX2-D2015-EC
1.5
3G3MX2-D2022-EC
2.2
3G3MX2-D2037-EC
3.7
3G3MX2-D2055-EC
5.5
3G3MX2-D2075-EC
7.5
3G3MX2-D2110-EC
11
3G3MX2-D2150-EC
15
3G3MX2-D4004-EC
0.4
3G3MX2-D4007-EC
0.75
3G3MX2-D4015-EC
1.5
3G3MX2-D4022-EC
2.2
3G3MX2-D4030-EC
3.0
3G3MX2-D4040-EC
4.0
3G3MX2-D4055-EC
5.5
3G3MX2-D4075-EC
7.5
3G3MX2-D4110-EC
11
3G3MX2-D4150-EC
15
ND (120% overload for 60s)
Rated current (A)
Max Motor (KW)
1.0
0.2
1.6
0.4
3.0
0.55
5.0
1.1
8.0
2.2
11.0
3.0
1.0
0.2
1.6
0.4
3.0
0.55
5.0
1.1
8.0
2.2
11.0
3.0
17.5
5.5
25.0
7.5
33.0
11
47.0
15
60.0
18.5
1.8
0.75
3.4
1.5
4.8
2.2
5.5
3.0
7.2
4.0
9.2
5.5
14.8
7.5
18.0
11
24.0
15
31.0
18.5
EMC filter*
Rated current (A)
1.2
AX-FIM1010-RE
1.9
AX-FIM1014-SE
3.5
AX-FIM1014-RE/SE
6.0
9.6
AX-FIM1024-RE/SE
12.0
1.2
1.9
AX-FIM2010-RE/SE
3.5
6.0
9.6
AX-FIM2020-RE/SE
12.0
AX-FIM2030-RE/SE
19.6
30.0
AX-FIM2060-RE/SE
40.0
AX-FIM2080-RE/SE
56.0
AX-FIM2100-RE/SE
69.0
2.1
AX-FIM3005-RE/SE
4.1
5.4
AX-FIM3010-RE/SE
6.9
8.8
AX-FIM3014-RE/SE
11.1
17.5
AX-FIM3030-RE/SE
23.0
31.0
AX-FIM3050-RE/SE
38.0
3