Screwless Terminals Connection - Omron 3G3MX2 Quick Start Manual

Born to drive machines; 200 v class three-phase input 0.1 to 15 kw; 200 v class single-phase input 0.1 to 2.2 kw; 400 v class three-phase input 0.4 to 15 kw
Hide thumbs Also See for 3G3MX2:
Table of Contents

Advertisement

MX2 Quick Start Guide
Type
Terminal Name
P24
PLC
Power
supply
L (upper row)
1
2
3/GS1
4/GS2
Input
5/PTC
6
7/EB
EA
11/EDM
12
CM2
Output
EO
AL0
AL1
AL2
Output AM
OI
Input
O
H
Power
supply
L (bottom row)

2.7 Screwless terminals connection

To connect cable, just push the terminal into position
To release cable, press the orange tab with small screwdriver and remove the cable
2.5 mm
12
Purpose
+24 V for logic inputs
Intelligent input common
GND for logic inputs
Discrete logic inputs
(Terminal [3],[4],[5] and [7] have dual function)
Pulse train input A
Discrete logic outputs [11]
(Terminal [11] has dual function. Selected by
hardware switch)
Discrete logic outputs [12]
GND for logic output
Pulse train output
Relay common contact
Relay contact, normally open
Relay contact, normally closed
Analog voltage output
Analog current input
Analog voltage input
+10 V analog reference
GND for analog signals
Push the screwdriver
Details
24VDC power supply for the DI
When source logic is selected, it becomes the common
point of input
(do not short to terminal L)
This terminal is used as the common terminal of the DI.
For internal supply (and voltage-free contacts):
Short between P24 and PLC: Sink logic (the current will flow from the MX2 input to the
output)
Short between CM1 and PLC: Source logic (the current will flow from the output to the
MX2 input)
Sum of input [1]~[7] currents (return)
It is possible to allocate any of the digital multifunction
inputs to this terminals.
When safety function is enable by hardware dip-switch
multifunction setting 77:GS1 amd 78:GS2 are compul-
sory for terminals 3 and 4 and functionality change
based on ISO13849-1
For PTC connect the motor thermistor between termi-
nals 5 and L and assign 19:PTC on parameter C005.
Inverter will trip when thermistor exceed 3kOhm.
For pulse train input B set 85:EB in C007 parameter.
Max freq for this terminal is 2kHz.
32 kHz max.
Common is [L]
Any multifunction output signal can be set to this ter-
minals.
In case the EDM is selected, the functionality is based
on ISO13849-1
50 mA max. ON state current, 27 VDC max. OFF state voltage
Common is CM2
100 mA: [11], [12] current return
10 VDC 32 kHz maximum
Any multifunction output signal can be set to this ter-
minals.
0~10 VDC
4 to 19.6 mA range, 20 mA nominal,
0 to 9.8 VDC range, 10 VDC nominal,
.
Sum of [OI], [O], and [H] currents (return)
Pull out the cable
Release the
screwdriver
Electrical specifications
Max 100mA including DI (5mA
each)
ON voltage: 18V min
OFF voltage: 3V max
Max.voltage: 27 VDC
Load current: 5mA at 24V
50mA max. ON state current,
27 VDC max. OFF voltage
2mA maximum
250 VAC 2.5 A(R load) max.
250 VAC 0.2 A (I load,P.F.=0.4)
100 VAC 10 mA min.
30 VDC 3.0 A(R load) max.
30 VDC 0.7 A(I load, P.F.=0.4)
5 VDC 100 mA
min
1 mA maximum
input impedance 100 W
input impedance 10 KW
10 VDC nominal, 10 mA max
MX2 Quick Start Guide