Deceleration to Stop
If the Stop Command is input (i.e., the Run Command is turned OFF) when b1-03 is set to 0, the motor decel-
erates to a stop according to the deceleration time that has been set. (Factory setting: C1-02 (Deceleration
Time 1))
If the output frequency when decelerating to a stop falls below b2-01, the DC injection brake will be applied
using the DC current set in b2-02 only for the time set in b2-04.
For deceleration time settings, refer to page 6-25 Setting Acceleration and Deceleration Times.
Run Command
Output frequency
ON
OFF
Decelerates to stop at
deceleration time
Fig 6.15 Deceleration to Stop
Stopping Methods
DC injection brake
DC injection brake time
when stopping (b2-04)