Inverter
Breaking Unit Application Precautions
When using a Braking Resistor Unit, create a sequence to detect overheating of the braking resistor and turn
OFF the power supply to the Inverter.
-22
2
Braking resistor overheat-
ing contacts (Thermal pro-
tector contacts)
Braking Unit #1
Cooling fin overheating con-
tacts (thermostat contacts)
Fig 2.15 Connecting Braking Units in Parallel
Three-phase power:
200 to 240 V, 50/60 Hz or
380 to 480 V, 50/60 Hz
Overload relay trip contact
of Braking Resistor Unit
* Use a transformer with 200 and 400 V outputs for the power 400 V Inverter.
Fig 2.16 Power Shutoff Sequence
Braking resistor overheat-
ing contacts (Thermal pro-
tector contacts)
Braking
Braking
Resistor
Resistor
Unit
Unit
Braking Unit #2
Cooling fin overheating con-
tacts (thermostatic contacts)
MCCB
MC MA
Fault contacts
Braking resistor overheat-
ing contacts (Thermal pro-
tector contacts)
Braking
Resistor
Unit
Braking Unit #3
Cooling fin overheating con-
tacts (thermostatic contacts)
R/L1
S/L2
T/L3
Inverter