The following only applies to Inverters with SPEC: E or later.
The operation after starting or stopping depends on the setting of b1-05 when flux vector control is selected
(A1-02 = 3).
Run Command OFF
Frequency reference
via analog input
0
(frequency reference)
b1-05=1
(Coast)
b1-05=2
(Run on E1-09)
b1-05=3
(Zero-speed)
Setting Precautions
When using flux vector control, the zero-speed control starts when motor speed drops to b2-01 during
deceleration. Also, the setting b2-01 < E1-09 is possible.
The current level during injection brake time at start is the value of E2-03 (motor no-load current). Accord-
ingly, b2-02 is invalid in flux vector control.
-20
6
b1-05=0
Injection brake
time at start
b2-03
Baseblock
Injection brake
time at start
Baseblock
b2-03
Injection brake
time at start
Baseblock
b2-03
Injection brake
time at start
Baseblock
b2-03
Fig 6.16 Deceleration to Stop (for Flux Vector Control)
ON
Zero-speed
control
b2-04
Frequency reference drops to less
than E1-09 and zero-speed control
Zero-speed
starts when motor speed drops to
control
b2-01.
b2-04
Zero-speed control
b2-04
OFF
E1-09
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Baseblock
Baseblock
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Zero speed control
Baseblock
b2-04
Run Command turns OFF
and zero-speed control starts
when motor speed drops to b2-01.
Baseblock