YASKAWA CIMR-F7A Instruction Manual page 129

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

Con-
Name
stant
Number
Set the limit value of the
voltage control range during
search operation.
Search
Perform search operation to
operation
optimize operations using
b8-06
voltage lim-
minute variations in voltage
iter
using energy-saving control.
Set to 0 to disable the search
operation. 100% is the motor
base voltage.
* 1. The factory setting is 1.0 when using flux vector control.
* 2. The factory setting is 2.00 s when Inverter capacity is 55 kW min.
The factory setting will change when the control method is changed. The open-loop vector factory setting is given.
* 3. By setting E2-11 (Motor rated output) the appropriate value will be set.
* 4. The factory setting depends on the Inverter capacity. The value for a 200 V Class Inverter of 0.4 kW is given.
Zero-Servo: b9
User constants for zero-servo functions are shown in the following table.
Con-
Name
stant
Number
Adjust the strength of the
zero-servo lock.
Enabled when the "zero-
servo command" is set for
the multi-function input.
When the zero-servo com-
mand has been input and the
Zero-servo
frequency reference drop
b9-01
gain
below excitation level (b2-
01), a position control loop
is created and the motor
stops. Increasing the zero-
servo gain in turn increases
the strength of the lock.
Increasing it by too much
will cause oscillation.
Sets the output width of the
zero-servo completion sig-
nal.
Enabled when the "zero-
servo completion (end)" is
set for a multi-function
input. The zero-servo com-
pletion signal is ON when
Zero-servo
the current position is within
b9-02
completion
the range (the zero-servo
width
start position± zero-servo
completion width.)
Set the allowable position
displacement from the zero-
servo start position to 4
times the pulse rate of the
PG (pulse generator,
encoder) in use.
Setting
Description
Range
0 to
100
Setting
Description
Range
0 to
100
0 to
16383
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vec-
tion
PG
0%
No
A
A
No
Control Methods
Change
Open
Factory
during
V/f
Loop
Setting
Opera-
V/f
with
Vec-
tion
PG
5
No
No
No
No
10
No
No
No
No
User Constant Tables
MEMO
BUS
Flux
Page
Regis-
Vec-
ter
tor
tor
No
1D1H 6-118
MEMO
BUS
Flux
Page
Regis-
Vec-
ter
tor
tor
A
1DAH 6-145
A
1DBH 6-145
5-
19