YASKAWA CIMR-F7A Instruction Manual page 365

Varispeed f7 general purpose inverter
Hide thumbs Also See for CIMR-F7A:
Table of Contents

Advertisement

o1-03 F3-01
2 to 39
x0040
to
x9999
(x = 0
to 3)
x1000
(x = 1
to 3)
DI-08 Reference Ranges
When using the DI-08, the following ranges can be set depending on the settings of the constants.
F3-01
0
1
2
3
4
5
6
7
-168
6
Switch
Reference Input Mode
S1
12 bits
3-digit BCD with sign, 1 rpm
-
16 bits
4-digit BCD with sign, 1 rpm
3-digit BCD with sign, 100%/(1- to 4-
-
12 bits
digit setting of o1-03)
4-digit BCD with sign, 100%/(1- to 4-
-
16 bits
digit setting of o1-03)
-
16 bits
4-digit BCD with sign, 100%/10000
Reference Input Mode
2-digit BCD with sign, 1%
2-digit BCD with sign, 0.1%
2-digit BCD with sign, 0.01%
2-digit BCD with sign, 1 Hz
2-digit BCD with sign, 0.1 Hz
2-digit BCD with sign, 0.01 Hz
8-bit binary with sign, 100%/255
Reference Setting
Range
-1599 to 1599 rpm
-15999 to 15999 rpm
-1599 to 1599
-9999 to 9999
(when o1-03 = 9999)
-1000 to 1000
Reference Setting Range
-110 to 110%
-15.9 to 15.9%
-1.59 to 1.59%
-159 to 159 Hz
-15.9 to 15.9 Hz
-1.59 to 1.59 Hz
-
-255 to 255
U1-01 Monitor Unit
o1-03 = 0
o1-03 = 1
1 rpm
1 rpm
5th digit of o1-03 set-
ting:
X = 0, unit: 1
X = 1, unit: 0.1
X = 2, unit: 0.01
X = 3, unit: 0.001
U1-01 Monitor Unit
o1-03 = 0
o1-03 = 1
0.01 Hz
0.01%

Hide quick links:

Advertisement

Table of Contents

Troubleshooting

loading

Table of Contents