Coaxial Test Settings - Fluke DTX Series User Manual

Hide thumbs Also See for DTX Series:
Table of Contents

Advertisement

DTX Series CableAnalyzer
Users Manual

Coaxial Test Settings

Table 3 describes the settings that apply to coaxial cabling
tests.
Setting
SETUP > Coaxial
Select the appropriate test limit for the job.
> Test Limit
SETUP > Coaxial
Select a cable type appropriate for the type you will test.
> Cable Type
SETUP > Coaxial
Nominal velocity of propagation, which is used with the measured propagation delay to determine
> NVP
cable length. The default value defined by the selected cable type represents the typical NVP for that
cable type. You may enter a different value if necessary. To determine the actual value, change the
NVP until the measured length matches the known length of a cable. Use a cable at least 30 m (100
ft) long.
Increasing the NVP increases measured length.
34
To access the settings, turn the rotary switch to SETUP, use
D
Table 3. Coaxial Cable Test Settings
Description
to highlight Coaxial; then press
H
.