Installation Requirements; Floor Protection; Clearances - Jøtul GF 305 DV IPI Installation And Operation Instructions Manual

Direct vent gas stove
Hide thumbs Also See for GF 305 DV IPI:
Table of Contents

Advertisement

5. Installation Requirements

Location
In selecting a location for the stove, consider the
following points:
1) Heat distribution
2) Vent termination requirements
3) Gas supply line routing
4) Traffic areas, furniture, draperies, etc.
The stove may be located on or near conventional
construction materials, however, proper clearance to
combustibles must be maintained in order to provide
adequate air circulation around the appliance. Also, it is
important to provide adequate access around the stove
for servicing and operation.
The clearance and hearth specifications listed in this
manual are the minimum requirements for combustible
material. A combustible material is anything that can
burn (i.e. sheet rock, wall paper, wood, fabrics etc.). These
surfaces are not limited to those that are visible and also
include materials that may be located behind non-com-
bustibles.
If you are not sure of the combustible nature of a
material, consult your local fire officials. Remember, "Fire
Resistant" materials are considered combustible: they are
difficult to ignite, but will burn. Also, "fire-rated" sheet
rock is considered combustible.

Floor Protection

This appliance CANNOT be installed directly on carpeting,
vinyl, linoleum or wood laminate flooring, such as Pergo.
If this appliance will be installed on any combustible
material OTHER THAN WOOD, a floor pad must be
installed that is either metal, wood, ceramic tile, stone, or
a listed hearth pad. This floor protection must extend the
full width and depth of the appliance. It is not necessary
to remove carpeting, vinyl or linoleum from underneath
the floor protection. See fig. 5.1.
24"
(610 mm)
Figure 5.1. Minimum combustible floor protection.
Stove and Vent Clearance
Requirements
Minimum Clearances from the Stove to Combustibles:
See figs. 5.2-4.
Rear:
Ceiling: 24 1/2" (622 mm)
Corner:
Right Side: 2" (51 mm)
Left Side:
- allows clearance to fully open the front door
Minimum Clearances between Vent Pipe and
Combustible Materials:
Horizontal Run:
Off the top of the pipe
Off the sides and bottom
Vertical Run:
All sides
18"
(457 mm)
Figure 5.2. Corner clearances.
139843_A GF 305 DV IPI 8/17
Measured from:
2" (51 mm)
Rear Shroud
Top Plate
3" (76 mm)
Side Plate
Side Plate
6" (152 mm)
Side Plate
2" (51 mm)
1" (25 mm)
1" (25 mm)
7