External pulsed resistors

With externally attached pulsed resistors, the power loss of the resistor that oc-
curs during braking accumulates outside the control cabinet and, thus, does not
place a thermal load on the control cabinet.
The external pulsed resistors are generally required for the 28 kW UI module.
Depending on the power requirement, up to two equal pulsed resistors can be
connected in the case of the 28 kW UI module. The protection function is para-
meterized via the connecting terminals.
Table 6-19
Data
Order number
Degree of protection acc. to
DIN EN 60529 (IEC 60529)
Weight [kg]
Type of cooling
Dimensions (W x H x D) [mm]
including the connecting cable
[m]
External PR 0.3/25 kW
Mounting
position
Note:
Carefully note the mounting position, base mounting is possible.
When mounting the pulsed resistor it must be carefully ensured that it is not located
in the cooling airflow of the drive group and there is sufficient clearance to the cable
ducts.
Fig. 6-19
Pulsed resistor, external
sales@aotewell.com
Technical specifications
0.3/25 kW (15 Ω)
6SN1113–1AA00–0DA0
(only for 28 kW UI module)
IP 54
3.4
Natural ventilation
80 x 210 x 53
3
Connecting cable
Industry Automation
6 Infeed Modules
6.7 DC link options
External pulsed resistor
Plus 1.5/25 kW (15 Ω)
6SL3100–1BE22–5AA0
IP20
5.6
Natural ventilation
193 x 410 x 240
5
External PR Plus 1.5/25 kW
Connecting cable