Mitsubishi QD51 Programming Manual page 349

Logic controller
Hide thumbs Also See for QD51:
Table of Contents

Advertisement

11 INSTRUCTIONS AND FUNCTIONS
Processing Code 4
11 - 179
Reading extension file register data
Control table format definition
Element position
Format 1
Format 2
%(0)
• • • • • • •
%(0)
%(1)
%(2)
%(3)
%(1)
%(4)
%(2)
%(5)
%(3)
%(6)
%(4)
%(7)
• It is possible to read data of extension file registers (file registers with block
number 1 or more) using this code.
• Specify the following data for <control table>.
Format 1 control table
%(0)
• • • • • •
%(1)
• • • • • •
%(2)
• • • • • •
%(3)
• • • • • •
%(4)
• • • • • •
Item
Station number
Control table
Network number
Station number
Detailed error code
Processing code
Block No.
Device number
Number of points
Specify the station number of the PLC CPU from which
data is to be read.
See Section 4.2.2 for the allowable specification range.
Processing code
• Specify 4.
Specify the block number of the extension file registers.
• If 0 is specified for the block No., the data in the file
registers of the PLC CPU is read.
(The same processing as reading R using the
processing code for reading device memory data will
be performed.)
• If a block number greater than 0 is specified, the data
in the extension file registers is read.
• The maximum value that can be specified for the block
No. varies depending on the memory cassette
mounted on the PLC CPU.
Specify the device number of the extension file registers.
The maximum value that can be specified for the device
number is the value set in the parameters of the PLC CPU.
The allowable specification range is from 0 to 8191.
Specify the number of device points to be read, including
the device specified in %(3).
The range that can be specified is from 1 to 64 points.
MELSEC-Q
Description
Specify the station number of the PLC.
Specify a control table of format 2.
Specify the network number.
Specify the station number of the PLC.
Detailed error codes are stored here.
Specify the processing code.
Specify the block number of the
extension file registers.
Specify the device number of the
extension file registers.
Specify the number of points to be read.
11 - 179

Advertisement

Table of Contents
loading

This manual is also suitable for:

Ad51h-s3Qd51-r24A1sd51s

Table of Contents