Positioning - Buderus Logano GE315 Installation And Maintenance Instructions Manual

Cast iron sectional boiler for oil or gaspressure jet burners
Table of Contents

Advertisement

2.3

Positioning

2.3.1 Plinth
Please maintain the recommended clearance from walls
when positioning the boiler to enable easy access for
installation and maintenance (
To assist boiler room tidiness the boiler should be
placed on a plinth 5 – 10 cm high (
plinth must be perfectly flat and level. The front edge of
the boiler should be flush with the edge of the plinth.
NOTE!
As an option we can offer a boiler plinth
designed to reduce transmitted noise.
You can cast a concrete plinth if the optional boiler plinth
is not used. When casting the plinth, you must
incorporate a steel angle with the dimensions
100 x 50 x 8 mm or a steel strip with the dimensions
100 x 5 mm (
Fig. 3 and the following table).
Number of
L
segments
5
6
7
8
9
Tab. 1
Dimensions of plinth and length of angular or flat
steel section
Logano GE315 - We reserve the right to make any changes due to technical modifications
Fig. 4).
Fig. 1, [1]). The
L
(length of
2
(plinth)
1
steel section)
[mm]
[mm]
970
730
1130
890
1290
1050
1450
1210
1610
1370
1
Fig. 3
Plinth dimensions [mm]
Installation
2
9