2.3
Positioning
2.3.1 Plinth
Please maintain the recommended clearance from walls
when positioning the boiler to enable easy access for
installation and maintenance (
To assist boiler room tidiness the boiler should be
placed on a plinth 5 – 10 cm high (
plinth must be perfectly flat and level. The front edge of
the boiler should be flush with the edge of the plinth.
NOTE!
As an option we can offer a boiler plinth
designed to reduce transmitted noise.
You can cast a concrete plinth if the optional boiler plinth
is not used. When casting the plinth, you must
incorporate a steel angle with the dimensions
100 x 50 x 8 mm or a steel strip with the dimensions
100 x 5 mm (
Fig. 3 and the following table).
Number of
L
segments
5
6
7
8
9
Tab. 1
Dimensions of plinth and length of angular or flat
steel section
Logano GE315 - We reserve the right to make any changes due to technical modifications
Fig. 4).
Fig. 1, [1]). The
L
(length of
2
(plinth)
1
steel section)
[mm]
[mm]
970
730
1130
890
1290
1050
1450
1210
1610
1370
1
Fig. 3
Plinth dimensions [mm]
Installation
2
9