Buderus Logano GE315 Installation And Maintenance Instructions Manual page 42

Cast iron sectional boiler for oil or gaspressure jet burners
Table of Contents

Advertisement

6
Maintenance
Remove the hot gas baffle by pulling it forward out of
the hot gas flues (Fig. 51, [1] – [4]).
Loosen the four self-tapping screws on the lower
boiler back.
Remove the boiler back.
Loosen the hook springs below the flue gas coupling
(see Fig. 33, page 24).
Pivot both ends of the thermal insulation upwards
(Fig. 52, [1]) and fix with the hook spring.
Remove the cleaning cover on the rear section
(Fig. 52, [2]) and the flue gas collector (Fig. 52, [3]).
Use the cleaning brushes.
You will find an illustration of the various types of
brushes offered by Buderus (optional accessory) in
Fig. 53.
42
Logano GE315 - We reserve the right to make any changes due to technical modifications
4
3
2
1
Fig. 55 Remove the hot gas baffles
3
Fig. 56 Cleaning cover removal
Fig. 57 Cleaning brushes
1
2

Hide quick links: