2.7

Boiler casing

This section describes how to fit thermal insulation and
casing components.
2.7.1 Support brackets
The edge of the front support brackets must point to the
front.
At the boiler front screw one further nut onto each tie-
bars (Fig. 30, [2]).
Insert the cross support bracket at the front on top of
the boiler (Fig. 30, [1]) between the first and the
second nut of the tie bars and secure on the cast lugs.
Tighten the outer nuts.
Secure the cross support bracket at the lower front
(Fig. 30, [3]) with two screws on the boiler section feet
of the front section.
Secure the upper rear support bracket (Fig. 31, [1])
on the cast lugs and with screws (M 8 x 15) on the
rear section.
The edge of the front upper support bracket must
point to the front.
Secure the lower support bracket (Fig. 31, [2]) with
two screws (M 8 x 15) to the feet of the rear section.
The edge of the lower support bracket must point to
the rear.