Installation
2.3

Positioning

2.3.1

Plinth

Please maintain the recommended clearance from walls
when positioning the boiler to enable easy access for
installation and maintenance (Fig. 4).
To assist boiler room tidiness the boiler should be placed
on a plinth 5 – 10 cm high (Fig. 3, Item 1). The plinth
must be perfectly flat and level. The front edge of the
boiler should be flush with the edge of the plinth.
NOTE!
As an option we can offer a boiler plinth
designed to reduce transmitted noise.
You can cast a concrete plinth if the optional boiler plinth
is not used. When casting the plinth, you must
incorporate a steel angle with the dimensions
100 x 50 x 8 mm or a steel strip with the dimensions
100 x 5 mm (see Fig. 3 and the following table).
Number of
L
segments
5
6
7
8
9
Fig. 1
Dimensions of plinth and length of angular or flat steel
section
We reserve the right to make any changes due to technical modifications.
Installation and maintenance instructions Logano GE315 • Issue 02/2006
L
(length of
2
(plinth)
1
steel section)
[mm]
[mm]
970
730
1130
890
1290
1050
1450
1210
1610
1370
1
Fig. 3
Plinth dimensions [mm]