2.4.2. Fill Rate
Defines the maximum rate at which the reported sensor value
increase. Allows you to adjust the SITRANS LR200 response to increases in the
actual material level. Fill Rate is automatically updated whenever Response
Rate is altered.
Options
Altered by:
Related
parameters
Enter a value slightly greater than the maximum vessel-filling rate, in units per
minute.
2.4.3. Empty rate
Defines the maximum rate at which the reported sensor value
decrease. Adjusts the SITRANS LR200 response to decreases in the actual
material level. Empty Rate is automatically updated whenever Response Rate
is altered.
Options
Altered by:
Related
parameters
Enter a value slightly greater than the vessel's maximum emptying rate, in units
per minute.
1)
The value produced by the echo processing which represents the distance from sen-
sor reference point to the target (see Sensor Mode (2.2.2.) on page 75 for an illustra-
tion).
2)
The value produced by the echo processing which represents the distance from sen-
sor reference point to the target (see Sensor Mode (2.2.2.) on page 75 for an illustra-
tion).
Page 78
SITRANS LR200 (HART) – INSTRUCTION MANUAL
Range: 0 to 99999 m / min.
Response Rate (2.4.1.)
*
Slow
Medium
Fast
Response Rate (2.4.1.)
Units (2.2.1.)
Range: 0 to 99999 m / min.
Response Rate (2.4.1.)
*
Slow
Medium
Fast
Response Rate (2.4.1.)
Units (2.2. 1 .)
1)
is allowed to
Fill Rate
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)
2)
is allowed to
Empty Rate
0.1 m/min (0.32 ft/min)
1.0 m/min (3.28 ft/min)
10.0 m/min (32.8 ft/min)