2)
Connect the wires to the terminals as shown:
the polarity is identified on the terminal block.
3)
Ground the instrument according to local
regulations.
4)
Tighten the gland to form a good seal.
Connecting HART
Typical PLC/mA configuration with HART
Notes
•
Depending on the system design, the power supply may be separate from the PLC,
or integral to it.
•
HART resistance (total of loop resistance, that is, cable resistance plus 250 Ohm
[resistor]) must be limited according to the allowable operating area as shown in
Curve 1 (General Purpose, Intrinsically Safe, Non-incendive)
either
Curve 2 (Flameproof, Increased Safety, Explosion-proof)
•
Do not connect more than one HART programming device at a time.
power supply
SITRANS LR200
7ML19985JP02
R = 250 Ω
SITRANS LR200 (HART) – INSTRUCTION MANUAL
on page 138.
active PLC
HART
modem
HART
communicator
cable shield
(if used)
on page 137 or
Page 21