Omron E3X-DRT21 Operation Manual page 73

Fiber amplifier sensor communication units
Table of Contents

Advertisement

CompoBus/S Remote I/O Communications
62
Node address:
Odd number
Node address – 1 Node address
Node address
Note If DIP switch pin 1 is ON (up to 14 Sensors connected), the same internal pro-
cessing is performed as for an Analog Terminal. Therefore, calculate the I/O
response time as for the Analog Terminal. (Calculate the I/O response time as
a normal Terminal when pin 1 is OFF.)
When DIP switch pin 1 is ON and the following masters are connected, the
Sensor Communications Error Flag and Sensor Communications Flag are not
synchronized with the ON/OFF data for Units 1 to 8.
• C200HW-SRM21 (pre-version 1) and CQM1-SRM21 (pre-version 1) Mas-
ter Control Units.
• SRM1-C0
(pre-version 1) and SRM1-C0
@
lers
• 3G8B3-SRM0
• C200PC-ISA
• SDD-CS1 Uniwire Send Unit (Manufactured by NKE Ltd.)
When a communications error occurs, for example, the data for Units 1 to 8
may be set to 0 before the Sensor Communications Error Flag has been
turned ON. If this is a problem, do not use the Unit with pin 1 set to ON (up to
14 Sensors connected).
Node address:
Bit
Even number
00
01
02
03
04
05
06
07
Node address +1 00
01
02
03
04
05
06
07
VME Board
@
2-SRM SYSMAC Board
@
Section 3-5
Contents
Unit 1 ON/OFF data
Unit 2 ON/OFF data
Unit 3 ON/OFF data
Unit 4 ON/OFF data
Unit 5 ON/OFF data
Unit 6 ON/OFF data
Unit 7 ON/OFF data
Unit 8 ON/OFF data
Unit 9 ON/OFF data
Unit 10 ON/OFF data
Unit 11 ON/OFF data
Unit 12 ON/OFF data
Unit 13 ON/OFF data
Unit 14 ON/OFF data
Sensor Communications Error Flag
Sensor Communications Flag
-V1 Programmable Control-
@