Omron E3X-DRT21 Operation Manual page 101

Fiber amplifier sensor communication units
Table of Contents

Advertisement

CompoWay/F Message Communications
Write Special Flags
Response Codes
Normal Completion
Error Completion
90
Writes the following settings for the Sensor of the specified unit number. This
command is possible with E3X-DA6TW and E3X-DA8TW Sensors only. An
error will occur if this command is written for any other Sensor.
Bit
00
Always 0.
01
Always 0.
02
Always 0.
03
Always 0.
04
Operating Mode Flag (one-word):
0: Dark-ON
1: Light-ON
05
Operating Mode Flag (two-word):
0: Dark-ON
1: Light-ON
06
Area Setting Flag:
0: AREA OFF
1: AREA ON
07
Always 0.
08
Always 0.
09
Always 0.
10
Always 0.
11
Always 0.
12
Always 0.
13
Always 0.
14
Always 0.
15
Always 0.
Response code
"0000"
Normal completion
Response
Error name
code
"1001"
Command too
long
"1002"
Command too
short
"1003"
Number of ele-
ments/data mis-
match
"1100"
Parameter error
Contents
Name
No error has occurred.
Cause
The command is too long.
The command is too short.
The number of data does not match the number
of elements.
The write data setting is out of range.
• Threshold setting out of range.
• Basic settings are out of range.
• Timer setting is not within limits.
• Hysteresis width is out of range.
• Custom Flags are out of range.
• Special Flags are out of range.
• Number of Sensors connected is more than 16.
• Response delay time is set to more than
100 ms.
Section 4-5
Description