Omron E3X-DRT21 Operation Manual page 121

Fiber amplifier sensor communication units
Table of Contents

Advertisement

Communications Timing
Maximum Refresh Cycle of Incident Light Level Data (E3X-DRT21 Only)
The following tables list the maximum values for the refresh cycle of incident light level monitoring when the
Unit is operating with remote I/O communications in two-word mode with incident light level monitoring (DIP
switch pin 1 OFF and pin 2 ON). The maximum refresh cycle of incident light level monitoring depends on
whether explicit messages are used and on the number of Sensors that are connected, as shown in the tables.
Using Explicit Messages
Number of Sensors
Maximum refresh cycle of
connected
1
50
2
100
3
160
4
240
5
330
6
430
7
540
8
670
9
2300
10
2500
11
3000
12
3300
13
3600
14
4200
15
4600
16
4900
Explicit messages are also used when the DeviceNet Configurator is connected.
Not Using Explicit Messages
Number of Sensors
Maximum refresh cycle of
connected
1
20
2
40
3
60
4
90
5
110
6
140
7
170
8
200
9
1500
10
1900
11
2000
12
2200
13
2300
14
2400
15
3000
16
3200
Note Normally, the incident light level refresh cycle is much shorter than the values listed in these tables.The
refresh cycles can be extended, however, with some timing settings. Consider the maximum refresh
cycle when designing the system.