Explicit Message Communications
1,2,3...
28
Service Code
When the command is completed normally, the value specified in the com-
mand with leftmost bit of the service code turned ON is stored as shown in the
following table.
Command service code
10 Hex
0E Hex
16 Hex
06 Hex
07 Hex
05 Hex
When an error response is returned to an explicit message, this value will be
94 Hex.
Data
Used to store read data only when a READ command has been sent.
Error Code
Specifies the explicit message error code. For details, refer to 2-6-5 List of
Error Codes.
Note
Set the DeviceNet message monitoring timer in the Fiber Amplifier Sensor
Communication Unit to 6 s minimum.
The procedure for setting the timer is as follows:
Using a CS1W-DRM21 or CJ1W-DRM21
Use the following procedure to set the timer from the DeviceNet Configurator.
1. Place the Configurator online by selecting Network and Connection.
2. Select and double-click either CS1W-DRM21 or CJ1W-DRM21.
3. Set the Fiber Amplifier Sensor Communication Unit node monitoring timer
to 6,000 ms.
Response service code
90 Hex
8E Hex
96 Hex
86 Hex
87 Hex
85 Hex