Configuration Parameters Cont.
8. Thermostat Diff Temp
The thermostat differential temperature is in units of 0.5 degrees
Fahrenheit. A value of 0x04 is 2.0F and 0x06 is 3.0F. The differential
temperature must be an integer value Non-integer values, such
as 1 5F (0x03), should not be used The supported values may vary
from thermostat to thermostat but typically, the allowed values are
2 0F (0x04) to 6 0F (0x0C)
9. Thermostat Recovery Mode
The Thermostat Recovery Mode can be either fast (0x01) or
economy (0x02)
10. Temp Reporting Filter (16-bit)
Set Command Definition
7
Command Class = COMMAND_CLASS_CONFIGURATION
Default
Precision (0x00)
Precision (0x00)
• Parameter (8-bit)
The parameter is set to 10 (0x0A) for the temperature
reporting filter.
• Default (1-bit)
If the default bit is set, the upper bound is zero (0) and the
lower bound is 124. This disables the filter.
• Size (3-bit)
The Size field must be set to 4 (100b).
• Precision (3-bits)
The precision field describes the precision of the temperature
filter value. The filter must be zero (0x00).
46
6
5
Command = CONFIGURATION_SET
Parameter = 0x0A
RESERVED
Temperature Filter Lower Bound
Temperature Filter Upper Bound
Vivint Element CT200 Operation Guide
4
3
Scale
Scale
Z-Wave
2
1
Size = 0x04
Bound Size (0x01)
Bound Size (0x01)
®
0