Special Control
3.5
Restart Standby
Restart is forced into standby to prevent the power from frequently turning on and off and to equalize pressure in
the refrigerant system.
Ta: Outdoor air temperature
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Ending conditions
3.6
Stopping Operation
Actuator operation is cleared when the system is down.
Outdoor unit actuator
Compressor
Outdoor fan
Four way valve
Main electronic expansion
valve
Subcooling electronic
expansion valve
Hot gas bypass valve
Ending conditions
43
Electric symbol
RXTQ36
RXTQ48
RXTQ60
TAVJU
TAVJU
TAVJU
M1C
M1C M1C OFF
M1F,
Ta > 30°C (86°F): STEP 4
M1F
M1F
Ta ≤ 30°C (86°F): OFF
M2F
Y1S
Y1S
Y1S Keep former condition.
0 pulse
Y1E
Y1E
Y1E
Y3E 0 pulse
Y2S
OFF
2 minutes
Electric symbol
RXTQ36
RXTQ48
RXTQ60
TAVJU
TAVJU
TAVJU
M1C
M1C M1C OFF
M1F,
M1F
M1F
M2F OFF
Y1S
Y1S
Y1S Keep former condition.
Y1E
Y1E
Y1E 0 pulse
Y3E 0 pulse
Y2S
OFF
Indoor unit thermostat is turned ON.
Operation
Operation
Functions and Control