Commission CPU 31x-2 DP as a DP slave in the PROFIBUS subnet as follows:
1. Switch on power, but hold the CPU in STOP mode.
2. First, switch on all other DP masters/slaves.
3. Now switch the CPU to RUN mode.
6WDUWXS RI &38 [ '3 DV '3 VODYH
When the CPU 31x-2x DP is switched to RUN, two independent operating mode
transitions are executed:
• The &38 switches from STOP to RUN mode.
• At the 352),%86'3 LQWHUIDFH the CPU starts data transfer with the DP
master.
5HFRJQL]LQJ WKH 2SHUDWLQJ 6WDWH RI WKH '3 PDVWHU (YHQW 5HFRJQLWLRQ
The table below shows how CPU 31x-2 operating as a DP slave recognizes
operating state transitions or data exchange interruptions.
Table 9-9
(YHQW
Bus failure interrupt
(short-circuit,
connector
unplugged)
DP master.
RUN → STOP
DP master
STOP → RUN
7LS:
When commissioning the CPU as DP slave, always program OB 82 and 86. This
helps you to recognize and evaluate the respective operating states or data
exchange errors.
9-28
Event recognition by CPUs 31x-2 DP acting as DP slave
Call of OB86 with the message 6WDWLRQ IDLOXUH
(coming event; diagnostic address of the DP slave, assigned to
the DP slave)
with I/O access: Call of OB122
(I/O access error)
Call of OB82 with the message 0RGXOH HUURU
(coming event; diagnostic address of the DP slave, assigned to
the DP slave; Variable OB82_MDL_STOP=1)
Call of OB82 with the message 0RGXOH 2.
(outgoing event; diagnostic address of the DP slave, assigned to
the DP slave; Variable OB82_MDL_STOP=0)
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
:KDW KDSSHQV LQ WKH '3 VODYH"