Using The Mode Selector Switch For A Cold Start (Cpu 318-2 Dp Only) - Siemens S7-300 Installation Manual

Automation system
Hide thumbs Also See for S7-300:
Table of Contents

Advertisement

&ROG UHVWDUW ZLWK &38  '3
With a CPU 318-2DP you can also perform a cold start instead of resetting the
memory.
Cold start means:
• The data blocks in the working memory created by SFC 22 are deleted. The
remaining data blocks have the default value from load memory.
• The process image and all timers, counters and memory bits are reset -
irrespective of whether they were configured as retentive.
• OB 102 is processed.
• The process image of the inputs is read before the first instruction in OB1 is
executed.
6WHS
1.
2.
3.
RUN
LED
On
Off
STOP
LED
On
Off
1
Figure 9-8 Using the mode selector switch for a cold start (CPU 318-2 DP only)
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01
Turn the key to STOP position
Turn the key to MRES position
Hold the key in this position until the STOP LED lights up for the second time
and remains on (this takes 3 seconds).
Then release the key.
You have to turn the switch to the RUN position within 3 seconds.
During start-up the RUN LED flashes at 2 Hz.
3 s
max. 3 s
2
3HUIRUPLQJ D &ROG 6WDUW
3 s
3
&RPPLVVLRQLQJ
t
9-15