&RQILJXULQJ
If the jumper is not installed, the reference potential of the S7-300 is connected
internally to the ground conductor via an RC system and the rail. This discharges
radio-frequency interference current and avoids static charge.
1RWH
To create a floating reference potential, remove the jumper from the CPU between
the M terminals and functional ground.
,VRODWHG RU QRQLVRODWHG PRGXOHV
,VRODWHG PRGXOHV
In configurations with isolated modules, the reference potentials of the control
circuit (M
$SSOLFDWLRQ UDQJH IRU LVRODWHG PRGXOHV
Use isolated modules for:
• All AC load circuits
• DC load circuits with a separate reference potential, for example:
DC load circuits whose sensors have different reference potentials (for
–
example if grounded sensors are located at some considerable distance
from the control system and no equipotential bonding is possible)
DC load circuits with grounded positive pole (L+) (battery circuits).
–
,VRODWHG PRGXOHV DQG JURXQGLQJ FRQFHSW
You can use isolated modules, regardless of whether or not the control system's
reference potential is grounded.
5-22
) and the load circuit (M
internal
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
) are galvanically isolated.
external
A5E00203919-01