Interfaces - Siemens S7-300 Installation Manual

Automation system
Hide thumbs Also See for S7-300:
Table of Contents

Advertisement

352),%86 '3 (OHFWULFDO FRQGXFWRU RU ILEHU RSWLF FDEOH"
Use fiber optic cables instead of copper conductors if you want your field bus to
cover greater distances regardless of the transmission rate and be insensitive to
external noise fields.
(TXLSRWHQWLDO ERQGLQJ
For information on what to take into account relating to equipotential bonding when
you configure your network, refer to the corresponding chapter in the appendix.
$OVR QRWH 
the section referring to communication in the relevant CPU manual.

,QWHUIDFHV
03, LQWHUIDFH
$YDLODELOLW\ ,Q DOO WKH &38V GHVFULEHG LQ WKLV GRFXPHQW
MPI (Multi-Point Interface) represents the interface between the CPU and a PG/OP
or for communication in an MPI Subnet.
The typical (default) transmission rate is 187.5 Kbps. You can also set the rate to
19.2 Kbps for communication with an S7-200. Other baud rates are not possible
(exception CPU 318-2DP: up to 12 Mbps).
The CPU automatically broadcasts its bus parameter configuration (e.g.
transmission rate) via MPI interface. A programming device, for example, can then
automatically retrieve the correct parameters and connect to an MPI Subnet.
1RWH
In RUN mode, you may only connect PGs to the MPI Subnet.
Other stations (e.g.. OP, TP, ...) should not be connected to the MPI subnet while
the PLC is in run mode. Otherwise, transferred data might be corrupted as a result
of interference or global data packages may get lost.