Note the following rules when working with intermediate memory:
• Assignment of address areas:
Input data of DP slaves are DOZD\V output data of the DP master
Output data of DP slaves are DOZD\V input data of the DP master
• The user can define these addresses. In the user program, access data with
load/transfer instructions or with SFC 14 and 15. You can also specify
addresses from the input/output process image (refer to Chapter $GGUHVVLQJ
8VHUGHILQHG $GGUHVVLQJ RI 0RGXOHV).
• The lowest address of specific address areas is their respective area start
address.
• The length, unit and consistency of the address areas for DP master and DP
slave must be identical.
1RWH
Assign transfer memory addresses taken from the DP address area of
CPU 31x-2 DP.
Addresses assigned to transfer memory cannot be assigned again to I/O
modules of CPU 31x-2 DP. When using consistent data areas in transfer
memory, note the section on &RQVLVWHQW 'DWD in Chapter $GGUHVVLQJ.
6 '3 PDVWHU
When exchanging consistent data with IM 308-C operating as DP master and
CPU 31x-2 DP as DP slave, note that:
You must program FB192 in IM 308-C to enable exchange of consistent data
between a DP master and the DP slave. FB192 reads or outputs CPU 31x-2 DP
data only in a single continuous block.
6 DV '3 PDVWHU
Bus parameters of an AG S5-95 operated as DP master must also be set in
CPU 31x-2 DP operating as DP slave.
'DWD WUDQVIHU LQ 6723 PRGH
The DP slave CPU goes into STOP mode: Data in CPU intermediate memory are
overwritten with "0". That is, the DP master reads "0".
The DP master goes into STOP mode: Actual data in CPU intermediate memory is
maintained and can still be read by the CPU.
9-32
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
A5E00203919-01