7HVWLQJ IXQFWLRQV DQG 'LDJQRVWLFV
Tip on OB 32 and OB 35: You can set the times in watchdog OB 32 and OB 35,
starting from 1 ms.
1RWH
The shorter the selected watchdog interrupt period, the more likely it is that
watchdog interrupt errors will occur. You must take into account the operating
system times of the CPU in question, the user program runtime and extension of
the cycle time by active PG functions, for example.
&URVVUHIHUHQFH
Details on the OBs and on SFCs required for their evaluation can be found in the
67(3  2QOLQH +HOS and in the Manual 6\VWHP 6RIWZDUH IRU 6  6\VWHP
DQG 6WDQGDUG )XQFWLRQV.
6WDWXV DQG HUURU GLVSOD\ RI '3FRPSOLDQW &38V
Table 11-5

The BUSF, BUSF1 and BUSF2 LEDs

/('
6)
 9'&
%86)
On
On
On/
flashe
s
On
On
-
On
On
-
Description of status X:
The LED can assume the status On or Off, but this status has no effect on the
current CPU function. For example, the states Force On or Off do not influence the
STOP status of the CPU
11-10
%86)
%86)
-
-
PROFIBUS DP interface error.
Remedy: Refer to the table below
On/
X
Error at the first PROFIBUS DP interface of CPU 318-2
flashes
DP.
Remedy: Refer to the table below
X
On/flash
Error at the second PROFIBUS DP interface of CPU 318-2
es
DP.
Remedy: Refer to the table below
S7-300 Automation System, Hardware and Installation: CPU 312IFM - 318-2 DP
'HVFULSWLRQ
A5E00203919-01