Communication
12.5.5

Integration of SIMOCODE pro as S7 slave via OM SIMOCODE pro

The "OM SIMOCODE pro" software must be installed to utilize the
advantages of SIMOCODE ES and parameterize SIMOCODE pro from the
STEP7 HW Config. OM SIMOCODE pro is included in the scope of supply
of the "SIMOCODE ES Premium" software.
Install the corresponding software.
The following table describes how you can insert SIMOCODE pro in
the STEP7 HW Config from the hardware catalog.
Step
1
2
3
4
Table 12-11: Integration of SIMOCODE pro as S7 slave via OM SIMOCODE pro
If SIMOCODE pro is integrated as an S7 slave you can use the routing
function in connection with SIMOCODE ES Premium. A prerequisite for
using this function is that a network connection (for example via Industrial
Ethernet) can be established between the PC with SIMOCODE ES installed
and the SIMATIC controller which supports routing.
In this manner, routing can be used to reach all SIMOCODE pro devices that
are connected to the controller.
12-20
Start STEP7 and open the "HW Config".
To integrate SIMOCODE pro as an S7 slave, navigate in the hardware
catalog in the "PROFIBUS DP > Devices > Motor Management System"
directory.
Enter
SIMOCODE pro C, SIMOCODE pro V (basic type 1) or
SIMOCODE pro V (basic type 2) on the PROFIBUS.
Only for SIMOCODE pro V:
SIMOCODE pro V can be connected in two basic types (basic type 1 or
basic type 2). See Chapter
Insert the desired basic type "basic type 1" or "basic type 2" as a module.
Only for the failsafe digital module DM-F PROFIsafe: Insert the desired
basic type "Basic type 1 - PROFIsafe" or "Basic type 2 - PROFIsafe" as a
module.
You can find further information on using DM-F PROFIsafe in the system
manual "Failsafe Digital Modules
SIMOCODE pro SAFETY".
Start the "SIMOCODE ES" software to generate the device parameters
with the "Parameters" button under "Parameters" in the object properties
of slot 4 of this S7 slave. The created parameters are incorporated in
STEP7 and are automatically transmitted to SIMOCODE pro during
startup
(see Chapter
12.8.3 "Parameter data during
STEP7
12.4.1 "Cyclic
data".
startup").