7.1.2
Basic setting
Set items, such as a network number and station number.
Project window
"Ethernet" under "Network Type".
Item
Network Type
Start I/O No.
Network No.
Group No.
Station No.
Mode
Remark
For settings to use the E71 in a redundant system, refer to the parameter settings for the redundant system function.
(
Page 220, Section 14.7.3)
[Parameter]
[Network Parameter]
Description
Select "Ethernet".
Set the start I/O number of the E71 in units of 16 points.
Set the network number of the E71.
Set the group number of the E71.
Set the station number of the E71.
Select the operation mode of the E71.
CHAPTER 7 COMMUNICATION PROCEDURE
[Ethernet/CC IE/MELSECNET]
Setting range
-
Within the number of I/O points of the
CPU module
1 to 239
0 to 32
1 to 64
• Online
• Offline
• Self-Loopback Test
• H/W Test
Select
7
83