(b) Router IP address
Set the IP addresses of the routers when the E71 communicates with the connected devices on other Ethernet
networks via a router other than the default router. Set the value that satisfies the following conditions.
• Condition 1: The IP address class is any of A, B, and C.
• Condition 2: The subnet address of the router is the same as that of the E71 on the own station.
• Condition 3: The host address bits are not all "0" or all "1".
● When the E71 communicates with the connected devices via a router in Passive open status, communications can be
performed without using the router relay function.
● The router relay function is not needed in a system that uses the Proxy router.