(b) If an error has occurred in the protocol setting data
Power on/reset
E71
Predefined protocol ready
(X1D)
Protocol setting data
check area
(address: 5320
to 533F
)
H
H
(2) When the protocol setting data is written
When the protocol setting data writing from GX Works2 is completed, Predefined protocol ready (X1D) turns off.
After the completion, the E71 checks the protocol setting data. If the protocol setting data is set correctly, the E71
turns on Predefined protocol ready (X1D).
If an error has occurred in the protocol setting data, Predefined protocol ready (X1D) stays off and the error
details are stored to the protocol setting data check area (address: 5320
(a) If the protocol setting data is set correctly
Start to write
the protocol setting data.
Writing the protocol
E71
X1D turns on when the
protocol setting data has been
set correctly before data write.
Predefined protocol ready
(X1D)
X1D turns off if no protocol setting data
has been set or an error has occurred in
the protocol setting data before data write.
Protocol setting data
check area
(address: 5320
to 533F
)
H
H
CHAPTER 11 DATA COMMUNICATIONS USING THE PREDEFINED PROTOCOL
Checking the
protocol setting data
Checking the protocol
setting data
setting data
X1D turns off.
Check result error
X1D stays off.
The error details are stored.
to 533F
H
H
Check result normal
X1D turns on when the
check result is normal.
The number of registered protocols and
information about whether protocols have
been registered are stored.
).
125
11