PILOT ADJUSTMENT

Periodically check the pilot flames. Correct
flame pattern has three strong blue flames:
1 flowing around the thermopile, 1 around
the thermocouple and 1 flowing across the
burner (it does not have to be touching the
burner).
Note:
If you have an incorrect flame
pattern, contact your FPI dealer for further
instructions.
Brûleur
Sonde de Flamme
Pilote

HIGH ELEVATION

This unit is approved in Canada for altitude to
4500 ft. (CAN/CGA-2.17-M91). For Natural Gas
installations above 4500 ft. follow current CAN/
CGA-B149.1.
1) 6 Stage flame adjustment
2) Pilot adjustment
3) Inlet Pressure Tap
4) Outlet Pressure Tap
5) Pilot Outlet
6) Main Gas Outlet
7) Main Gas Inlet
B36XTE -NG10 System Data
Conversion Kit # 576-969
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Max. Input Rating
Min. Input Rating
Supply Pressure
Manifold Pressure
(High)
Manifold Pressure
(Low)
Allumage
B36XTE - LP10 System Data
For 0 to 4500 feet altitude
Burner Inlet Orifice Sizes:
Max. Input Rating
Min. Input Rating
Supply Pressure
Manifold Pressure
(High)
Manifold Pressure
(Low)
885 S.I.T. VALVE
DESCRIPTION
4
3
#35
31,000 Btu/h
21,500 Btu/h
min.5.0" w.c.
3.5"+/- 0.2" w.c.
1.6"+/- 0.2" w.c.
#51
3 1 , 0 0 0 B t u / h
25,000 Btu/h
min.11.0" w.c.
10"+/- 0.2"w.c.
6.4"+/- 0.2"w.c.
2
1
installation
GAS PIPE PRESSURE
TESTING
The appliance must be isolated from the gas
supply piping system by closing its individual
manual shut-off valve during any pressure
testing of the gas supply piping system at
test pressures equal to or less than 1/2 psig.
(3.45 kPa). Disconnect piping from valve at
pressures over 1/2 psig.
The manifold pressure is controlled by a regulator
built into the gas control, and should be checked
at the pressure test point.
Note: To properly check gas pressure, both
inlet and manifold pressures should
be checked using the valve pressure
ports on the valve.
1) Make sure the valve is in the "OFF" position.
2) Loosen the "IN" and/or "OUT" pressure
tap(s), turning counterclockwise with a 1/8"
wide flat screwdriver.
3) Attach manometer to "IN" and/or "OUT"
pressure tap(s) using a 5/16" ID hose.
4) Light the pilot and turn the valve to "ON"
position.
5) The pressure check should be carried out
with the unit burning and the setting should
be within the limits specified on the safety
label.
6) When finished reading manometer, turn
off the gas valve, disconnect the hose and
tighten the screw (clockwise) with a 1/8" flat
screwdriver. Note: Screw should be snug,
but do not over tighten.
4
3
2
1
5
6
Regency Bellavista™ B36XTE-10 Gas Fireplace
|
39