7.18 Setting Record - Biasi Inovia 25S ERP User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for Inovia 25S ERP:
Table of Contents

Advertisement

9
10
11
12 13
Fig. 7.46
• Scroll the various parameters using keys 15
or 16 until the letters P12 are displayed on
the LCD display and the value of the param-
eter (100=Inovia 25S ERP), indicating that
"parameter 12" (Fig. 7.47) has been acti-
vated.
Fig. 7.47
• It is possible to modify parameter using keys
9 or 10 (Fig. 7.46) (Refer to Fig. 7.44 and
determine the correct Value appertaining to
the output required for the central heating
requirement.).
• By pressing key 12 (Fig. 7.46) confirmation
of the inserted value is obtained.
• Press keys 15 or 16 (Fig. 7.46) to exit with-
out changing the value.
• Exiting the "programming mode" is auto-
matic, after 15 minutes, or by cutting power.

7.18 Setting record

Important: at the end of the setting opera-
tion it is important to fill/update the table
COMMISSIONING
(Fig. 7.48).
17
This to allow a correct setting of this boiler
in case of replacement of the main control
16
p.c.b.
PARAMETER
15
Boiler type
14
Water sensors con-
figuration
Pump management
TA/OT zone manage-
ment
Gas type
Not used
C.h. flow max temper-
ature °C
Factory
reset
Chimney sweep func-
tion
C.h.
quency
C.h. pump post-circu-
lation
Max. useful output in
c.h. mode
C.h. pump working
type
Ignition power
K
probe diagram)
Regulation of the mini-
mum heating power
D.h.w. burner turn off
function
NTC on the c.h. return
User interface
Not used
Not used
Not used
Not used
DIGIT
P 01
P 02
P 03
P 04
P 05
P 06
P 07
parameters
P 08
P 09
reignition
fre-
P 10
P 11
P 12
P 13
P 14
value
(external
P 15
P 16
P 17
P 18
P 19
P 20
P 21
P 22
P 23
VALUES
---------------
---------------
---------------
---------------
---------------
- 65 -