setting made with keys 15 and 16 for a K 1,5
is shown in Fig. 7.24.
Sequence for setting the K coefficient with
the remote control connected
Act on the programming of the REMOTE con-
trol to select the setting of the K coefficient.
• Electrically feed the boiler by activating the
bipolar switch envisioned during installation.
• Press button
for more than 3 seconds to
enter in
(Fig. 7.25) mode.
0
21
3
1
8
6
1 5
9
1
2
Fig. 7.25
to display the K REG win-
Press button
dow (Fig. 7.26).
Fig. 7.26
It is possible to change the value using but-
tons
and
.
Press button
to exit from mode
7.26).
7.11 Setting the pump post-circula-
tion
The pump, in heating function, is set for a
post-circulation of about one minute at the end
of each heat request.
- 60 -
COMMISSIONING
This time can be changed by a minimum of
zero to a maximum of four minutes by acting
on programming both from the panel controls
and the remote control.
• Enter in "programming mode" by pressing
keys 12 - 15 - 16 (Fig. 7.27) for 10 seconds
at the same time until the letters P01 are
displayed on the LCD display, indicating that
"parameter 01" (Fig. 7.28) has been acti-
vated.
9
10
11
Fig. 7.27
Fig. 7.28
• Scroll the various parameters using keys 15
or 16 until the letters P11 are displayed on
the LCD display, indicating that "parameter
11" (Fig. 7.29) has been activated.
(Fig.
Fig. 7.29
• It is possible to modify parameter 11 by
00=0s to 99=255s using keys 15 or 16
(each increase or reduction by a unit on the
12 13
17
16
15
14