7.10 Setting the K coefficient of the
external temperature probe
The boiler is set with a K coefficient equal to
zero for boiler functioning without the probe
connected.
If the boiler is NOT EQUIPPED with the re-
mote control (optional) refer to Fig. 7.18.
- 58 -
COMMISSIONING
until a setting of 60 is
C.h. flow temperature °C
K=6
K=4 K=3
80
70
60
50
40
30
20
20
15
10
5
0
External temperature °C
Fig. 7.18
If the boiler is EQUIPED with the remote con-
trol (optional) refer to Fig. 7.19.
In this case K setting must be done from the
remote control.
C.h. flow temperature °C
K=6
K=4
K=3
80
70
60
50
40
30
20
20
15
10
5
0
External temperature °C
Fig. 7.19
The K coefficients is a parameter that increas-
es or reduces the boiler flow temperature
when the outside temperature changes.
When installing the external probe it is neces-
sary to set this parameter based on the effi-
ciency of the heating plant in order to optimise
the flow temperature (Fig. 7.19).
E.g. In order to have a flow temperature at the
heating plant of 60°C with an external tem-
perature of -5°C, set a K at 1.5 (sectioned line
in Fig. 7.19).
Sequence for setting the K coefficient
• Enter in "programming mode" by pressing
K=2
K=1,5
K=0,5
-5
-10
-15
-20
-25
K=2
K=1,5
K=1
K=0,5
-5
-10
-15
-20
-25