Gas Conversion; Warnings; Operations And Gas Setting - Biasi Inovia 25S ERP User Manual And Installation Instructions

Wall hung, fanflue, roomsealed, high efficiency gas boiler
Hide thumbs Also See for Inovia 25S ERP:
Table of Contents

Advertisement

8

GAS CONVERSION

8.1

Warnings

The commissioning of this boiler and
system must only be undertaken by a
Gas Safety Registered Engineer, quali-
fied to work on Liquefied Petroleum Gas
(LPG) in accordance with the require-
ments of the Gas Safe Installation and
Use Regulations.
Components used to adapt it to the type
of gas available must be genuine parts
only.
Factory setting = Natural gas.
8.2

Operations and gas setting

Check that the gas cock mount-
ed on the gas piping to the boil-
er is closed and that the appli-
ance is not powered.
• Remove the body's front panel and turn
the control panel as shown in section
"MAINTENANCE" to page 69.
• Unscrew the connector C, remove the
fixing fork A and remove the pipe B (Fig.
8.1).
Fig. 8.1
• Carry out gas conversion by correctly re-
placing the gas restrictor (Fig. 8.2), refer-
GAS CONVERSION
Fig. 8.2
The factory boiler is set for functioning
with Natural gas (G20).
A
To set the functioning of the boiler with LPG
(G31) gas, carry out the following settings:
B
C
• Enter in "programming mode" by pressing
ring to the "Technical Data" section page
28 (Inovia 25S ERP).
Attention, to reassemble repeat
the operations carried out in re-
verse order. Be careful not to
damage the OR gasket of the gas
pipe when inserting the pipe in the
air box (air/gas mixer). After any
service operation on the compo-
nents of the gas circuit check all
the connections for gas tightness.
keys 12 - 15 - 16 (Fig. 8.3) for 10 seconds
at the same time until the letters P01 are
displayed on the LCD display, indicating
that "parameter 01" (Fig. 8.4) has been
activated.
Gas restrictor
- 67 -