90° =--- 0,85 m
ø 60 mm
45° =--- 0,65 m
Fig. 6.14
In the last section, the fumes are expelled
through a vertical section.
Extensions and elbows can be added to ex-
tend the kit's length.
The chart of Fig. 6.15 gives the allowable
dimensions of the ducts "a" and "b" of (Fig.
6.14).
"a" vertical length (m)
11
10
9
8
7
6
5
4
Allowedvalues
o
3
2
1
0
0
1
2
3
4
Fig. 6.15
Each additional elbow reduces the overall
acceptable length of the flue system as fol-
lows:
INSTALLATION
90° =--- 1 m
ø 60/100 mm
45°
=--- 0,5 m
d
e
5
6
7
8
9
10
"b" horizontal length (m)
45° (60/100 mm) reduce length by 0,5 m.
90° (60/100 mm) reduce length by 1 m.
45° (60 mm) reduce length by 0,65 m.
90° (60 mm) reduce length by 0,85 m.
6.9

Electric connection

• Unscrew screws "P" and remove the front
panel "Q" by pulling it and pushing it to-
wards the top so that it is freed from the
top housing Fig. 6.16.
11
Fig. 6.16
P
Q
- 43 -