Fig. 7.23
It is possible to change the value using but-
tons
and
.
Press button
to exit from mode
7.23).
7.11 Setting the pump post-circula-
tion
The pump, in heating function, is set for a
post-circulation of about one minute at the end
of each heat request.
This time can be changed by a minimum of
zero to a maximum of four minutes by acting
on programming both from the panel controls
and the remote control.
• Enter in "programming mode" by pressing
keys 12 - 15 - 16 (Fig. 7.24) for 10 seconds
at the same time until the letters P01 are
displayed on the LCD display, indicating that
"parameter 01" (Fig. 7.25) has been acti-
vated.
COMMISSIONING
9
10
11
Fig. 7.24
(Fig.
Fig. 7.25
• Scroll the various parameters using keys 15
or 16 until the letters P11 are displayed on
the LCD display, indicating that "parameter
11" (Fig. 7.26) has been activated.
Fig. 7.26
• It is possible to modify parameter 11 by
00=0s to 99=255s using keys 15 or 16
(each increase or reduction by a unit on the
display corresponds to 2.5 seconds). Ex.
17=42 seconds.
• The writing P11 - SEt alternates on the dis-
play (Fig. 7.27).
12 13
17
16
15
14
- 65 -