imum of 55°C.
• Enter "programming mode" by following the
procedure indicated in section "Accessing
installer parameters" on page 43.
18
12
13
Figure 5.41
• Press 12 and hold until the LCD display
shows the code A02, indicating entry into
"parameter A02" (Figure 5.42).
Figure 5.42
• Use 15 or 16 (Figure 5.41) to change the
value of parameter A02:
01 = high temperature (50/80°C)
02 = low temperature (25/55°C)
03 = complete temperature set (25/85°C)
(factory setting)
• Press 12 or 13 (Figure 5.41) to confirm the
value entered and return to the list of param-
eters (Figure 5.42).
• Press 17 (Figure 5.41) to exit "programming
mode".
5.21 Setting pump post-circulation
The pump, in heating mode, is set for a
post-circulation of about one minute at the end
- 48 -
INSTALLATION
17
16
15
RESET
bar
of each heat request.
This time can be programmed from a mini-
mum of zero to a maximum of 99 seconds.
• Enter "programming mode" by holding down
17 and 18 for 5 seconds at the same time
(Figure 5.43). The code P00 appears on
the display, indicating entry into "parameter
P00" (Figure 5.44).
18
12
13
Figure 5.43
Figure 5.44
• Scroll through the various parameters using
12 or 13 until the LCD display shows the
code P03, indicating entry into "parameter
P03" (Figure 5.45).
Figure 5.45
• Press 16 (Figure 5.43) to show the value of
parameter P03 on the LCD display (Figure
5.46).
17
16
15
RESET
bar
RESET
bar