Figure 5.42
Use buttons
and
Press to exit
mode (Figure 5.42).

5.18 Setting pump post-circulation

The pump, in heating mode, is set for a post-cir-
culation of about one minute at the end of each
heat request.
This time can be changed from a minimum of
10 seconds to a maximum of 20 minutes in pro-
gramming mode, using either the control panel
or the remote.
• Enter "programming mode" by pressing the 13
and 15 keys simultaneously for 5 seconds (Fig-
ure 5.43) until HiS (Boiler History) appears on
the LCD display (Figure 5.44).
12
13
Figure 5.43
- 54 -
INSTALLATION
to change the value.
17
16
15
14
Figure 5.44
• Scroll through the various menus by pressing
the keys 13 (back) or 15 (forward), until PAr
(Parameters menu) appears on the LCD display
(Figure 5.45).
• Press the 14 key for 1 second to enter the se-
lected menu.
Figure 5.45
• Scroll through the various parameters by press-
ing the keys 13 (back) or 15 (forward), until P12,
which alternates with the parameter value, ap-
pears on the LCD display (Figure 5.46).
Figure 5.46
• Press the 14 key for 1 second (Figure 5.43) to
enter the selected parameter. The display will
show the following (Figure 5.47).