B. Mantel Projections (All Fronts)
WARNING! Risk of Fire! Comply with all minimum clear-
ances as specified. Framing closer than the minimums list-
ed must be constructed entirely of non-combustible materi-
als (i.e., steel studs, concrete board, etc.).
Combustible Mantels Above Appliance Outer Wrap
(All Fronts)
Note: All
measurements
in inches.
12 IN. MAX.
6 IN. MAX.
3 IN.
MAX.
1 IN.
MAX.
12 IN. MIN.
9 IN. MIN.
MEASUREMENTS FROM TOP
OF APPLIANCE OUTER WRAP
APPLIANCE OUTER WRAP
SHEET ROCK
Figure 10.3 Minimum Vertical and Maximum Horizontal
Dimensions of Combustibles
48
22 IN. MIN.
TO CEILING
18 IN. MIN.
15 IN. MIN.
Heatilator • ION-V7, ION-S7, ION-H7 Installation Manual • 2276-980 Rev. E • 5/15
Non-combustible Mantels Above Appliance
Outer Wrap (All Fronts)
Note: All
measurements
in inches.
12 IN. MAX.
9 IN. MAX.
6 IN.
9 IN. MIN.
MAX.
4 IN.
6 IN. MIN.
MAX.
*1/2 IN. (STUDIO & FRAME FRONT)
SEE FIGURE 10.10 FOR CLEARANCE (RADIUS FRONT)
MEASUREMENTS FROM TOP
OF APPLIANCE OUTER WRAP
APPLIANCE OUTER WRAP
SHEETROCK
*1/2 IN. GAP IS NEEDED FOR DECORATIVE FRONT
INSTALLATION AND REMOVAL.
Figure 10.4
Minimum Vertical and Maximum Horizontal
Dimensions of Non-Combustibles
22 IN. MIN.
TO CEILING
12 IN. MIN.