Recommended Water Conditions - FULTON FHE-250 Installation, Operation & Maintenance Manual

Gas fired condensing boiler 250 kw
Table of Contents

Advertisement

5
5.4

RECOMMENDED WATER CONDITIONS

It is very important that a strict water management program is followed to ensure trouble free boiler
pH Value
Hardness
Suspended Solids
Chloride
Organic Matter
Oil
Silica
Page 68
! IMPORTANT
Recommended Water Conditions
operation.
The following are recommended for feedwater/boiler water
mg/kg = Milligrams per Kilogram
CaCO
= Calcium Carbonate
3
SiO
= Silicon Dioxide
2
For practical purposes mg/kg = ppm
FHE-250 MANUAL 09 2014 ISSUE 2
8.5 to 9.5 tested at room temperature.
less than 2.0 mg/kg in the form of CaCO
None
Less than 50 mg/kg
Less than 5 mg/kg
None
Less than 180 mg/kg, in the form of SiO
3
2