Recommended Water Conditions - FULTON VMP Series Installation, Operation And Maintenance Manual

Vertical multi-port fuel fired steam boiler
Table of Contents

Advertisement

J Series & Electric Steam Boilers

Recommended Water Conditions

It is very important that a strict water management program is followed to ensure trouble free boiler operation.
pH Value
Hardness
Suspended Solids
Chloride
Organic Matter
Oil
Minimum Temperature
pH Value
Hardness
Suspended Solids
Chloride
Oxygen Scavenger, Sodium Sulphite
Tannin
Phosphate
Total Alkalinity
Caustic Alkalinity
Total Dissolved Solids (TDS)
Iron
Silica
Dissolved Oxygen
mg/kg
CaCO
PO
4
SiO
PPM
1 Grain hardness
therefore 70 ppm
For practical
purposes ppm
Fulton Ltd
5 Fernhurst Road, Fishponds, Bristol.
BS5 7FG. England.
Every effort is made to ensure accuracy at time of going to press. However as part of our policy of continual product improvement, we reserve the right to alter specifications without prior notice.
Page 90
The following are recommended for feedwater and for boiler water
FEEDWATER (water entering boiler)
BOILER WATER (water inside boiler)
KEY
=
Milligrams per Kilogram
=
Calcium Carbonate
3
=
Phosphate
=
Silicon Dioxide
2
=
Parts Per Million
=
17.118 ppm
=
4.10 grains hardness
=
mg/kg
Telephone:
Fax:
E-mail:
Website:
Technical Information
!
IMPORTANT
8.5 to 9.5 tested at room temperature.
Less than 2.0 ppm in the form of CaCO
None
Less than 50 ppm.
Less than 5 ppm.
None
85 °C
10.0 to 12.0 tested at room temperature.
Not detectable.
Less than 100 ppm.
Less than 500 ppm.
30 to 70 ppm.
30 to 70 ppm
30 to 70 ppm, in the form of PO
Less than 1000 ppm.
Minimum 300 ppm as CaCO
Less than 2000 ppm.
Less than 1 ppm.
Less than 150 ppm, in the form of SiO
None
It is critical that the boiler water pH be
alkaline in the range 10.0 - 12.0.
Daily boiler blowdown is essential to
help prevent formation of deposits
and reduce Total Dissolved Solids
(TDS).
Consult your water treatment specialist
to establish the frequency and duration
of blowdown required to achieve the
required conditions.
+44 (0) 117 972 3322
+44 (0) 117 972 3358
sales@fulton.co.uk
www.fulton.co.uk
Fulton Ltd
Sheet No. 139 Issue 4
.
3
.