5. Drain and flush the water side of the heat exchanger as required (separate from system flush) using
clean water only.
6. Take a sample of the system fluid and verify the water quality is in compliance as defined in
C.
7. Inspect and clean the condensate system and check for leaks. If a condensate neutralization kit is
present, open the lid and inspect the limestone rocks. If they are absent or have been significantly
worn away, replace them with new limestone rocks. Use high-calcium (or pure) limestone.
8. Examine the venting system. Refer to the vent manufacturer's instructions for requirements in addition
to those listed below.
a. Check all joints and pipe connections for tightness.
b. Check pipe for corrosion or deterioration. If any piping needs replacing, do so immediately.
c. Inspect and clean any screens in the vent terminal.
9. Qualified service personnel should thoroughly inspect the heating system and correct any problems
prior to re-starting the boiler.
10. Qualified service personnel should thoroughly inspect the heating system and correct any problems
prior to re-starting the boiler.
11. Perform combustion analysis and readjust as necessary according to the Combustion Setup and
Adjustment combustion settings table.
Refer
to
Section 3.12.2 Combustion Setup and
It is recommended that a copy of this report is filed for future reference.
12. Perform a leak test of the gas valves in accordance with the manufacturer's instructions.

5.2 Preventive Maintenance

Proper maintenance schedule and record keeping is critical for optimum
performance and to maintain the HARSCO Industrial, Patterson-Kelly
warranty.
The blower motor is permanently lubricated and does not require periodic
lubrication.

5.2.1 Daily Preventive Maintenance

Observe operating temperature and general conditions. Make sure that the flow of combustion and intake air
to the boiler are not obstructed. Determine the cause of any service codes or lockouts on the display panel.
Observe any unusual noises or operating conditions and make the necessary corrections. Notify responsible
individuals for required corrective action or repair.

5.2.2 Weekly Preventive Maintenance

Observe the conditions of the main flame. A normal high fire flame is mostly orange with a blue halo, while at
low fire the burner will glow yellowish-orange.
Correct air adjustment is essential to the efficient operation of this boiler. Ensure that the flow of combustion
and ventilation air is not obstructed.
If an adjustment in the combustion appears necessary, the flue gas composition should be checked with a
carbon dioxide (
) or oxygen (
CO
2
and Adjustment combustion settings table. If an adjustment to the combustion is necessary, call a qualified
Adjustment.
N
OTICE
NOTE
) analyzer and compared to the values stated in the Combustion Setup
O
2
P-K SONIC